Shop brain

Setup values

These are the numbers and station facts Derek's rules still need. A fleet value applies everywhere. A station value replaces it at that station. A unit value replaces both for that piece of equipment.

Back to Rules

Box → air handler

Each box and the air handler the rules use for it, with where that came from. The rules try, in this order: a confirmed link, the Setup answer for which air handler serves each box, the station tree, the only air handler on the station, then a box name that fits one air handler only, such as VAV-2-01 for AHU-2. A box whose name fits more than one air handler, or none, waits for a link. An owner or an admin can confirm the air handler for any box, or clear a confirmed link so the rules go back to the next source. A fan is never an air handler.

No stations are loaded, so boxes cannot be listed.

Temperature units

Temperatures with no unit are °F (default) or °C

A temperature that carries its own unit always uses it. This setting is only for points that send a number with no unit. They are read as °F unless the station, or the device, is set to °C here. Set every station that reports in °C.

Every station reads °F, the default.

Loading setup values.

Air handling units and DOAS

Cooling capacity shortfall

Which zones each AHU serves (to count '≥ 25% of zones')

per-site setup. This rule stays off until it has an answer.

MAT sensor fault

Which AHUs have a preheat coil upstream of the MAT sensor (to skip them)

per-site setup

Missed economizer

Economizer high limit per AHU

value from Derek. This rule stays off until it has an answer.

Missed economizer

OA damper minimum position per AHU (BAS min-position points found at 14 sites, need mapping)

per-site setup. This rule stays off until it has an answer.

Economizing above high limit

Economizer high limit per AHU

value from Derek. This rule stays off until it has an answer.

Economizing above high limit

OA damper minimum position per AHU

per-site setup. This rule stays off until it has an answer.

Low outdoor air

Minimum OA fraction per AHU

value from Derek. This rule stays off until it has an answer.

Low outdoor air

OA damper minimum position per AHU

per-site setup. This rule stays off until it has an answer.

Fan maxed, static low

Which boxes each AHU serves

per-site setup. This rule stays off until it has an answer.

Static reset not working

Static SP reset maximum per AHU ('at max')

value from Derek. This rule stays off until it has an answer.

Static reset not working

Occupied hours (occupancy point or schedule)

per-site setup

Static reset not working

Which boxes each AHU serves

per-site setup. This rule stays off until it has an answer.

Freeze protection

OA damper minimum position per AHU (MAT branch only)

per-site setup

Filter loaded or blown out

Filter final resistance or clean baseline per filter bank

value from Derek. This rule stays off until it has an answer.

No ventilation while occupied

Which units are 100% recirculation (to skip)

per-site setup

OA open in warm-up or unoccupied

Warm-up / cool-down mode status per AHU

per-site setup

Building pressure out of range

Occupied hours where no occupancy point exists (Site R)

per-site setup

Humidifier failed or stuck

Duct RH high limit per AHU (read from each AHU's own high-limit point; the high-limit half is off where there is none)

per-site setup

DOAS dehumidification shortfall

Leaving dewpoint SP per DOAS

value from Derek. This rule stays off until it has an answer.

DOAS dehumidification shortfall

Which units are DOAS

per-site setup

Broken or slipping belt

Fan kW baseline at each speed

value from Derek. This rule stays off until it has an answer.

Motor drawing high power

Fan/pump kW baseline at each speed

value from Derek. This rule stays off until it has an answer.

Coil valves open with fan off

Freeze-protection mode status per AHU

per-site setup

Overcooling: supply air well below setpoint with the chilled water valve open

How far below its setpoint supply air has to be to count as overcooling, per unit (5°F unless set)

per-site setup

VAV boxes, zones and terminal units

Zone too warm

Which AHU serves each zone (for 'AHU fault-free')

per-site setup. This rule stays off until it has an answer.

Zone too warm

Occupied hours (occupancy point or schedule)

per-site setup

Zone too cold

Occupied hours (occupancy point or schedule)

per-site setup

Starved box

Which AHU serves each box (for 'AHU static at SP')

per-site setup. This rule stays off until it has an answer.

Reheat failure

Which AHU serves each box (for SAT)

per-site setup. This rule stays off until it has an answer.

Leaking reheat valve

Which AHU serves each box (for SAT)

per-site setup. This rule stays off until it has an answer.

Reheat during cooling

Cooling maximum airflow per box (BAS points like 'CLG FLOW MAX' exist at some sites)

per-site setup. This rule stays off until it has an answer.

Rogue zone

Occupied hours (occupancy point or schedule)

per-site setup

Night setback not applied

Occupancy schedule (scheduled occupied/unoccupied times, not just the occupancy command)

per-site setup. This rule stays off until it has an answer.

Electric reheat failure

Which AHU serves each box/zone

per-site setup. This rule stays off until it has an answer.

Electric heat without airflow

Heating minimum airflow per box

per-site setup. This rule stays off until it has an answer.

Electric heat without airflow

Which AHU serves each box/zone

per-site setup. This rule stays off until it has an answer.

Zone setpoint pushed to an extreme

Lowest occupied cooling setpoint before it counts as pushed to an extreme, per zone (68°F unless set)

per-site setup

Zone setpoint pushed to an extreme

Highest occupied heating setpoint before it counts as pushed to an extreme, per zone (76°F unless set)

per-site setup

Zone setpoint pushed to an extreme

Which zones run setpoints outside the comfort range on purpose, such as labs or server rooms (to skip)

per-site setup

Box damper not following its command

Gap between a box damper's command and its position feedback that counts as not following, per box (20 points unless set)

per-site setup

Chilled water and central plant

Low ΔT syndrome

Design CHW ΔT per plant

value from Derek. This rule stays off until it has an answer.

Low ΔT syndrome

How to get plant load % (chiller RLA at Customer D and 1300 Example St; elsewhere needs capacity)

per-site setup

High condenser approach

Baseline condenser approach per chiller

value from Derek. This rule stays off until it has an answer.

High evaporator approach

Baseline evaporator approach per chiller

value from Derek. This rule stays off until it has an answer.

Chiller efficiency loss

Baseline kW/ton per chiller and the load / CW-temp bin sizes

value from Derek. This rule stays off until it has an answer.

High tower approach

Design tower approach

value from Derek. This rule stays off until it has an answer.

Condenser water too cold

Chiller manufacturer's minimum CWST

value from Derek. This rule stays off until it has an answer.

Tower fan control failure

CWST setpoint at Customer D (none found)

per-site setup

Over-staged plant

Capacity of each chiller / boiler

value from Derek. This rule stays off until it has an answer.

Over-staged plant

How to measure total plant load

per-site setup. This rule stays off until it has an answer.

Lead/lag not rotating

Which units are lead/lag pairs

per-site setup

Chilled water pump running with no chiller and no demand

Which chilled water pumps run with the chillers off on purpose (waterside economizer or heat exchanger), to skip

per-site setup

Chilled water supply setpoint stuck low in cool weather

Outdoor air temperature below which a low chilled water supply setpoint is flagged, per plant (65°F unless set)

per-site setup

Chilled water supply setpoint stuck low in cool weather

Chilled water supply setpoint at or below which it counts as stuck low, per plant (42°F unless set)

per-site setup

Chilled water supply setpoint stuck low in cool weather

Which plants are process or data-center plants (to skip)

per-site setup

Heating plant, pumps and loops

Condensing boiler not condensing

Which boilers are condensing

per-site setup. This rule stays off until it has an answer.

HWST too hot

Steam vs non-steam per system

per-site setup

High flue temperature

Flue temp baseline per firing rate

value from Derek. This rule stays off until it has an answer.

Loop pressure loss

Fill pressure per loop

value from Derek. This rule stays off until it has an answer.

WSHP loop out of range

Design WSHP loop band per site (Derek's 'typically 60–90°F' is a guide, not the per-site number)

value from Derek. This rule stays off until it has an answer.

Hot water supply setpoint stuck high in mild weather

Outdoor air temperature above which a high hot water supply setpoint is flagged, per plant (60°F unless set)

per-site setup

Hot water supply setpoint stuck high in mild weather

Hot water supply setpoint at or above which it counts as stuck high, per plant (170°F unless set)

per-site setup

Hot water supply setpoint stuck high in mild weather

Which plants have year-round high-temperature loads (to skip)

per-site setup

Hot water pump running in warm weather with no heating demand

Outdoor air temperature above which a hot water pump with no heating demand is flagged, per plant (70°F unless set)

per-site setup

Hot water pump running in warm weather with no heating demand

Which hot water loops have a year-round load, such as a domestic hot water heat exchanger or process (to skip)

per-site setup

RTUs, heat pumps and refrigerant

Aux heat overuse

Morning recovery window

per-site setup. This rule stays off until it has an answer.

Heating and cooling stages together

Dehumidification-reheat / defrost status per unit

per-site setup

Abnormal subcooling

Manufacturer's subcooling target per unit

value from Derek. This rule stays off until it has an answer.

Compressor running below its low-ambient lockout

Outdoor air temperature below which a running compressor is flagged, per unit (40°F unless set)

per-site setup

Compressor running below its low-ambient lockout

Which units have a real low-ambient kit (to skip)

per-site setup

Unit flipping between heating and cooling

Changes between heating and cooling within 2 hours that count as flipping, per unit (3 unless set)

per-site setup

Unit flipping between heating and cooling

Separate 2-hour windows in a day that need that many changes, per unit (2 unless set; 1 drops the two-window rule)

per-site setup

Sensors and operations

OAT sensor error

Night-hours window

value from Derek. This rule stays off until it has an answer.

Poor IAQ

OA damper minimum position per AHU (CO2 branch)

per-site setup

Critical spaces and safety

Critical room overheat

Critical-room tags per site (only rooms named Server/IT/Elev/Data found so far)

per-site setup

Pressure relationship reversed

Which rooms are pressure-critical and their required sign

per-site setup. This rule stays off until it has an answer.

Kitchen makeup air failure

Which MAU serves each hood

per-site setup. This rule stays off until it has an answer.

Sensors, controls and network

Setpoint outside sane limits

Design max static SP per AHU

value from Derek

Setpoint outside sane limits

Steam vs non-steam per system

per-site setup

Reading at rest

Span per sensor

value from Derek. This rule stays off until it has an answer.

Reading at rest

Which fan / pump serves each sensor

per-site setup. This rule stays off until it has an answer.

SAT sensor drift

Which AHU serves each box/zone

per-site setup. This rule stays off until it has an answer.

RAT sensor drift

Ducted vs plenum return per AHU

per-site setup. This rule stays off until it has an answer.

RAT sensor drift

Which AHU serves each box/zone

per-site setup. This rule stays off until it has an answer.

Optimal start too early

Occupancy schedule (scheduled occupied/unoccupied times, not just the occupancy command)

per-site setup. This rule stays off until it has an answer.